Q. Can I
install underfloor heating in both old and new buildings?
A. Yes, but it is best installed in buildings that
have good insulation. Well insulated modern buildings cool at a much
slower rate and are not subject to excessive swings in temperature
when outside temperature conditions change.
Q. Can a standard boiler be used for an underfloor
heating system?
A. Yes, wall mounted or floor
mounted, gas or oil fired, combination boilers or standard boilers
can be used, but the biggest advantage in efficiency will be obtained
when a condensing gas or oil fired type is used as these boilers
can take advantage of the lower return water temperatures occurring
on underfloor heating systems.
Q. I am designing an apartment complex
where space is at a premium. What is the smallest boiler I can use
for underfloor heating?
A. There is an electric boiler
on the market, that measures one metre long by 90mm square, that
will run an underfloor heating system. It only weighs 9kg and is
available in sizes 6kw, 9kw, 11kw and 12kw.
Q. What are the main components of an underfloor heating
system?
A. Boiler, pipework, manifolds
and the control system.
Q. What pipe do you use for underfloor heating systems?
A. Multilayer pipe which is aluminium
sandwiched between layers of PEX pipe. All pipes should incorporate
an oxygen barrier to prevent oxygen ingress into the system.
Q. Do underfloor heating systems operate at a lower temperature
than a radiator system?
A. Yes, radiator systems will
operate at a boiler flow temperature of 82°C and a temperature
drop of 11°C, but an underfloor heating system will run at temperatures
in the range of 35°C to 60°C depending on floor conditions
and the type of building.
Q. Why do I need to use manifolds?
A. All the buried pipework in
underfloor heating systems should be in continuous loops without
joints. The flow and return from each loop of pipe is brought back
to manifolds where the flow of water can be monitored and controlled.
Individual rooms or areas can have their own room thermostats for
local temperature control wired to low voltage actuator heads on
the flow control valves. The advantages of using manifolds are that
areas which are not required to be heated can be shut off, local
modifications and additional pipe loops can be added without the
need to drain the entire system, and the system can be balanced
quickly and efficiently.
Q. What is the maximum loop length?
A. The maximum loop length of
100m must be used in all installations. It is not advisable to make
the loops longer than 100m. The reason for this is due to the head
pressure from the pump, the pump used is only capable of pressurising
water through 100m of pipe. 100m of pipe will cover an area of approximately
25m2. For commercial installations where larger diameter pipe is
used, the maximum is 140 metres.
Q. What are the lengths of each loop?
A. The pipe is marked every metre.
This makes it very easy to check the length of each loop. When laying
the pipe it is important to mark how long each loop is, this is
to allow the flow gauges to be easily adjusted to the right levels
The maximum length of a loop for domestic installations is 100 metres.
For commercial installations the lengths can be longer, up to 140
metres, but a larger diameter pipe is used and the very large systems
have booster pump sets.
Q. What type of insulation is to be used?
A. Use 50mm high density insulation
below the pipes and 65 - 75mm of screed on top of the insulation.
All installation work must comply with current Building Regulations.
The mixing valve needs to be set at minimum temperature when commissioning
the system. Increase the temperature by 2 to 3 degrees everyday.
This will avoid the screed cracking.
Q. What is the water flow temperature?
A. The water flow temperature
will vary between 35-60°C, depending on the heat losses from
the building. If the system operates with thermostatic mixing valves,
use 43°C temperature for screeded floors and 55°C temperature
for timber suspended and floating floors.
Q. What is the heat output?
A. Maximum heat output from screeded
floors is approximately 100 W/m2, the maximum heat output from timber
suspended floor and floating floor is 70 W/m2. With there being
higher standards of insulation in new buildings, average heat requirements
for many buildings are now below 60 W/m2. For small bathrooms it
is standard practice to also install warm water towel rails to give
extra heat output as these areas are usually not very large.
Q. How do you fill the underfloor heating system?
A. The system should be filled
with water and fully vented of air. This can best be achieved using
mains water pressure through the two end caps on the manifold. All
valves should be closed and the flow end cap connected with a hose
to mains water, with the return end cap connected to a hose laid
to waste water point. One by one flow and return valves are opened
and closed on loop purging them of air.
Q. What is the working life of our pipe?
A. Our pipe has one of the highest
approvals in the world from the Water Research Council (WRAC); 10
bar pressure and 95°C temperature. Our pipe is guaranteed for
50 years. When correctly installed and run, our pipe should have
a working life in excess of between seventy years and one hundred
years, provided that no oxygen has seeped into the pipe and that
the system has not been run at excessive temperatures.
Q. Can you combine an underfloor heating system with radiators?
A.Yes, but there must be filters installed to avoid
sludge from the radiators blocking the underfloor pipes.
Q. What is the required spacing between pipes on an underfloor
heating circuit?
A.We recommend pipe centres of 200mm. Within 500mm
of an external wall, pipe spacing should be reduced to 100mm
Q. Why should pipes be spaced closer together adjacent to
external walls?
A. This is necessary to offset heat losses through
glazing, external doors, patio doors etc.
Q. Why do I need to put insulation below the underfloor
heating circuit?
A. Insulation will reduce heat loss through the
floor construction, resulting in lower fuel bill. Also, the insulation
assists in deflecting heat upwards resulting in quicker warm up
periods and assisting in producing a constant floor surface temperature.
Insulation is also essential to produce a floating slab construction.
Q. What does ‘floating slab construction’ mean?
A. The screed containing the underfloor heating
circuits is separated by insulation underneath and around the perimeter
from any part of the building structure. This allows the screed
to expand and contract during the operation of the underfloor heating
system without cracking or breaking up. This method of floor construction
is called a ‘floating slab’
Q. What is a control pack?
A. A control pack consists of a pump, thermostatic
mixing valve, zone valve and isolating vales combined with pipe
fabrication to enable the control pack to connect directly to the
manifolds
Q. What does a control pack do?
A. Thermostatic mixing valve – the thermostatic
mixing valve ensures that the water circulates through the underfloor
heating circuit at a constant temperature of 43 degrees C. This
results in a floor surface temperature that is even and does not
exceed 29 degrees C, or 27 degrees C for wooden floors.
Zone valve – the zone valve allows the underfloor
heating system to be isolated via a programmer or room thermostat.
The zone valve can also be utilised to send a signal to the boiler
to fire when open.
Pump – the pump circulates water through
the underfloor heating system. It also creates a head pressure,
which overcomes the resistance created by the circuit, vales and
manifold.
Isolating valves – the isolating valves
allow the underfloor heating system to be isolated manually.
Q. Why should the surface temperature of the floor be controlled
to keep it below 29 degrees C?
A. Feet dispense a lot of heat from the body. If
the temperature of the floor is above 29 degrees C, the body has problems
dispersing heat through feet. As a result people often complain of
aching legs if the floor surface temperature is too high
Q. What temperature is your pipe rated to?
A. 10 bar pressure.
Q. When testing the installation prior to laying screed, what
pressure do you test the system at?
A. The pressure test should be twice the working
pressure with a minimum of 6 bar. During the laying of the screed,
this pressure shall be applied to the pipes.
Q. What are the minimum and maximum temperatures for laying
screeding?
A. The minimum is 3 degrees C and the maximum is
35 degrees C.
Q. How much does it cost to run an underfloor
heating system?
A. Depending on the installation, and underfloor heating system is
between 15% and 40% cheaper to run than a conventional radiator system.
This is because an underfloor heating system works at much lower water
temperature.
Q. What are the benefits of underfloor heating compared to a radiator
system?
A. Space - radiators take up 15% of room space. Health - underfloor
heating kills 80% of dust mites. Aesthetics - decorate as often as
you please without having to remove and replace radiators. Cost Effective
- energy savings of between 15% and 40%; system costs comparable if
anything other than bog standard radiators being compared. Project
Cost Savings - when allowing for labour cost in both first and second
fix.
Q. What happens when your pipe gets clogged
with limescale?
A. The inner layer of our pipe is polyethylene and limescale can not
attach itself to it - hence no clogging of pipe.
Q. How strong is your pipe?
A. The manufacturer of our pipe illustrates the strength of it by
showing an elephant standing on it. But this is more than a sales
gimmick. Once l |